DATASHEET (PDF) |
THE INDUSTRY’S MOST POPULAR FUSE FOR MOTOR CIRCUIT PROTECTION.
Tri-onic® SmartSpot® fuses now provide a visual
open fuse indicator. With advanced material technology
added to the existing product the TR and TRS
current limiting time delay fuses are engineered for
overcurrent protection of motors and transformers,
service entrance equipment, feeder and branch
circuits. Tri-onic proven time delay characteristic
safely handles harmless starting currents and inrush
currents associated with today’s motors and
transformers.
Features/Benefits
- Solid State SmartSpot Indicator
- Time delay for motor start-ups and transformer inrush
currents without nuisance opening
- Current limiting for low peak let-thru current
- Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
- Easy-to-read label for quick recognition
and replacement
- Metal-embossed date and catalog number for
traceability and lasting identification
- Fiberglass body provides dimensional stability in
harsh industrial settings
- High-grade silica filler ensures fast arc quenching and
high current limitation
- AC & DC Rated
|
Applications
- Motor Circuits
- Mains
- Feeders
- Branch Circuits
- Transformers
- Service Entrance
Equipment
- General-purpose
Protection
Ratings
- TR
- AC: 1/10 to 600A 250VAC, 200kA I.R.
- DC: 1/10 to 2 8/10A& 35 to 400A, 250VDC,
20kA I.R.; 3 to 30A &
450 to 600A, 160VDC, 20kA I.R.
- TRS
- AC: 1/10 to 600A 600VAC, 200kA I.R.
- DC: 1/10 to 12A,
600VDC, 20kA I.R.;
15 to 60A, 300VDC, 20kA I.R. 70 to 600A, 600VDC, 100kA I.R.
Approvals
- UL Listed to Standard
248-12 File E2137
- CSA Certified to
Standard C22.2
No. 248.12
- DC Listed to UL
Standard 248 TRS only
|