PGFS-73105
Sensata / AIRPAXGround Fault Circuit Interrupter-Permanent Splice ...
DESCRIPTION
The LineGard™ 30 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured by North Shore Safety, Ltd., a leader in innovated safety products. The unique design offers the flexibility of splicing in protection of a GFCI anywhere within the length of the circuit run, making it ideal for both new and existing applications. Unlike breaker style GFCI’s which have limitations of circuit length from the service panel, the PFGS series can be integrated directly into a circuit or paired in tandem with an approved receptacle and enclosure. Rated Current Up to 30 Amps or rating of wiring device and/or cable Horse Power 1HP@120 VAC, 3HP@240 VAC Trip Level 5mA +/–1mA Operating Frequency 60 Hz Reset Type1 Automatic or Manual Phase Dual voltage and 3 phase Response Time 25mS max Operating Temperature –35°C to 66°C Operating Voltage Range 85% to 110% of rated VAC Let-Go Voltage 60% of supply voltage Open Neutral Protection Trips upon loss of neutral
Search Keywords: PGFS73105
SPECIFICATIONS
IN STOCK: 2
Ships today, if you order in
Factory Lead-Time 2 Weeks
English